WATER SUPPLY SYSTEMS, PREOPERATIONAL TEST, PROCEDURE 910

by U.S. DEPARTMENT OF ENERGY/SOUTHERN CALIFORNIA EDISON COMPANY,

Technical Report, 1981

Barcode

CSP Unique ID 190682966

Status

Electronic Resource

Call number

**Click on MARC view for more information on this report.**

Publication

DOE SF 10499 T121; Report; July 1981.

Language

Library's review

ABSTRACT:
OBJECTIVES -
• Demonstrate that Raw Water Storage Tank (TK-701) level is maintained at proper level through the operation of LV-1702.
* Demonstrate Raw Water Storage Tank local level indicator LI-170J, Low Leve] Alarm Functions LAL 1701A and LAL 17018 and high level alarm function
Show More
LAH-1703
* Demonstrate manual operation of Raw/Service Water Pumps P-703 and P704 and related interlock function.
* Demonstrate standby mode operation of Raw/Service Water Pumps P-703 and P-704 and rejected interlock function.
* Demonstrate minimum flow recirculation through PV-1703 and related interlock function.
* Demonstrate that Raw/Service Water Pump head rises are as desjgned (P-703 and P-704).
* Demonstrate that PV-1704 will provide the Package Make-up Demineralizer with service water at the design pressure.
• Demonstrate that the Makeup Package Demineralized (D-701) is capable of producing demineralized water at the specified capacity and at or below the specified water chemistry limits.
• Demonstrate operation of the conductivity monitoring CI-1205 and high conductivity alarm functions CAH-1205.
• Demonstrate the operation of the Demineralized Water Storage Tank (TK-702) level control LV-1203 and interlock functions.
• Demonstrate the Demineralized Water Storage Tank (TK-702) high/Jaw level alarm and local indicator functions.
• Demonstrate manual operation of the Demineralized Water Transfer Pump (P-710) and the related interlock function.
• Demonstrate that the Demineralized water transfer pump (P-710) head pressure is as designed.
• Demonstrate that the polishing demineralizers are capable]e of producing condensate at the specified capacity and at or below the specified water chemistry limits.
• Demonstrate operation of the conductivity monitoring CI-1206 and high conductivity alarm functions CAH-1206.
• Demonstrate that high conductivity effluent from the polishing demineralizer will cause automatic recirculation and the excessive rinse alarm function QAH-1206.
• Demonstrate the condensate storage tank (TK-902) inlet level control function, LC-162.
• Demonstrate the condensate storage tank (TK-902) remote and local level indicating and alarm functions.
• Demonstrate safety shower and eye wash are operational.
Show Less